Connectivity
What OpenSy reads, how, and how far it has been tested.
Each row states the access path, what comes back, the limits, and whether it has been run on real equipment.
Inputs
Controllers and drives.
A route to one controller or one drive uses one seat on the license. Several machines on the same controller share that seat.
| Equipment | Access | What is read | Limits | Test status |
|---|---|---|---|---|
| ControlLogix and CompactLogix | EtherNet/IP. Direct, or routed through one or more chassis. | Controller tags by name, including members of structures. The tag list is browsed from the controller. | A fast signal can be read every 5 ms. Text tags are read on the machine scan. | Measured on benchLive plant controller |
| Kinetix 6500 drives | EtherNet/IP, routed to the drive through its ControlLogix chassis. | Axis attributes: output current, voltage, and power, DC bus voltage, torque, position, velocity, axis state, faults, alarms, and motor nameplate. | No faster than every 100 ms. These drives have no parameter-number list. Each drive uses one seat. | Run on hardware |
| Modbus TCP devices | Modbus TCP. | Holding registers, in blocks of up to 125 words. 16-bit and multi-word values, and ASCII text. | Read on the machine scan. Automatic range detection stops at an illegal-address reply or at 125 words. | Run on hardware |
| PLC-5 and SLC on DH+ | EtherNet/IP to a ControlLogix chassis, then a 1756-DHRIO on channel A or B. | Data files by address: integer (N), bit (B), float (F), timer (T), and counter (C). | No tag browse. A file-range scan reads up to 32 words. Read on the machine scan. | Run on hardware |
Timed sample rates for the ControlLogix fast path are in the test record. PowerFlex-class parameter reads still have automated tests only, and are listed under what is not included.
Discovery
How a controller is found.
OpenCast scans the industrial PC’s own machine subnet. A device is listed only when it answers Modbus or EtherNet/IP. An open port alone is not listed.
- Bounded
- Scans stay on the local subnet, with a deadline and a limit on parallel connections.
- Read only
- Discovery does not write a value, create a mapping, or commission a machine.
- Chassis and DH+
- Choosing a ControlLogix chassis lists its modules. Choosing a 1756-DHRIO lists the active DH+ stations on both channels.
- Tested per endpoint
- A connection test is tied to the exact address and route it ran against. Change the route and the test must be run again.
Output
What goes to the plant network.
The industrial PC carries its own MQTT broker. Plant systems subscribe to it when the plant network is connected.
- Named signals
- Every mapped signal is published by name under the plant, site, area, line, and cell. The machine’s structure is published too, so a subscriber can discover it.
- Scan and fast channels
- Machine telemetry is published once per scan. A fast signal has its own channel. It publishes when the value changes, and once a second while it holds.
- Events
- Scrap entries from the operator are published as events alongside telemetry.
Scope
What is not included.
- Writes to a controller or drive
- OpenSy reads. It does not write tag values, send commands, or open an I/O connection.
- SLC 5/05 on Ethernet
- SLC and PLC-5 are read on DH+ through a 1756-DHRIO. A direct Ethernet SLC is not in this release.
- Text from PLC-5 and SLC files
- Integer, bit, float, timer, and counter files are read. String files are not.
- Sparkplug B
- Signals are published as JSON on MQTT. Sparkplug B encoding is not included.
- PowerFlex on hardware
- Parameter reads for PowerFlex-class drives pass automated tests. They have not been run on a drive.
- Other protocols
- A controller outside this page is a conversation with engineering, not a claim made here.