Test record

What was tested, on what, and what it showed.

Each entry gives the setup, the measured result, and what the run does not prove. Results are stated as measured.

Test hardware

Linux plant IPC and Windows bench IPC.

OpenSy has been run on both platforms. The timed ControlLogix and welder figures below were measured on the Windows Cincoze. Clean install and controller bring-up were also run on the Linux plant IPC.

Linux plant IPC
Ubuntu Server / Debian with Docker Engine. Used for plant-style install and bring-up of the full system.
Windows bench IPC
Cincoze DC-1200. Intel Pentium N4200, 4 cores at 1.10 GHz, 8 GB. Windows 10 Enterprise LTSC with containers on Hyper-V.
Software under test
The full OpenSy system, with history, on both platforms.

Results

Test runs.

Bench

Fast signal from a ControlLogix on the same switch

The Windows Cincoze bench IPC and a ControlLogix on one switch. One signal read every 5 ms for 20 seconds. Five runs.

Samples per second
198
Sample spacing, median
5 ms
Sample spacing, 99th percentile
6 ms
PLC read to MQTT subscriber, median
2.8 ms
Samples lost through the broker or into history
None
Worst gap across the five runs
7 to 14 ms
Gaps longer than 10 ms
About 1 in 4,000

What this run shows. The long gaps were single PLC reads that came back late. A routed controller or a slower network raises the read round trip and lowers the rate.

Live controllerNovember 11, 2026

Routed read from a live plant welder

The Windows Cincoze bench IPC, on a plant network. EtherNet/IP into a ControlLogix chassis, then across the backplane and a second Ethernet module to the welder’s controller on another subnet. One floating-point tag, weld current, read every 5 ms. Three 10-second rounds, then one 30-second sample.

Read round trip, median
10.0 ms
Read round trip, 95th percentile
12.7 ms
Read round trip, 99th percentile
21.9 ms
Published samples in 30 seconds
300, or 10.0 per second
Publish spacing, median
100.2 ms
Edge collector processor load
10 to 12%
Edge collector memory
About 29 MiB
Memory growth over a 60-second monitor
None

What this run shows. The fast channel publishes when a value changes, and once a second while it holds. Weld current moved about ten times a second, so that is the published rate. This run shows that routed reads are healthy. It does not show 200 samples a second on a routed path.

Hardware

Kinetix 6500 drive attributes

Kinetix 6500 control modules, catalog 2094-EN02D-M01S0, read through a ControlLogix chassis. Each attribute is one read-only request.

Attributes answered
Every attribute in the supported list
Covered
Output current, voltage, and power. DC bus voltage. Torque. Position and velocity. Axis state, status, faults, and alarms. Motor nameplate.
Time per attribute
About 5 ms

What this run shows. These drives do not answer the parameter object, so they have no parameter-number list. PowerFlex-class parameter reads pass automated tests and have not been run on a drive.

Hardware

Modbus TCP holding registers

Modbus TCP devices on the machine network, read from the industrial PC. Holding-register blocks mapped in OpenCast and published on the machine scan.

Access
Modbus TCP
What was read
Holding registers, including multi-word and ASCII values
Where it ran
On hardware, from the industrial PC

What this run shows. This path is used on real devices. Timed sample-rate figures for Modbus are not published here; Modbus stays on the machine scan and does not use the 5 ms fast channel.

Hardware

PLC-5 and SLC on DH+ through a 1756-DHRIO

PLC-5 and SLC data files reached over EtherNet/IP into a ControlLogix chassis, then across a 1756-DHRIO on DH+. File addresses mapped in OpenCast and read on the machine scan.

Access
1756-DHRIO channel A or B
What was read
Integer, bit, float, timer, and counter files
Where it ran
On hardware, from the industrial PC

What this run shows. This path is used on real controllers. A direct Ethernet SLC is not included. Timed sample-rate figures for DH+ file reads are not published here; those files stay on the machine scan.

BenchNovember 11, 2026

Clean install from the customer package

A clean install from the same installation package a customer receives. Run on the Windows bench IPC, and on the Linux plant IPC with Docker Engine.

Full system with history
Started healthy
OpenCast
Reachable after install
First controller
Commissioned and reporting
Platforms
Linux plant IPC and Windows bench IPC

What this run shows. The customer package carries the built software and the installer. Nothing is built on site.

Lab, simulated sensorNovember 11, 2026

High-rate sensor capture

A sensor sidecar on the Windows Cincoze bench IPC, sampling every 5 ms and publishing batches of four over MQTT with broker acknowledgement. One 30-second run. The source was a sensor simulator on the same PC.

Samples captured per second
200.0
MQTT messages per second
50.0
Sample spacing, median
5.0 ms
Sample spacing, 99th percentile
9.83 ms
Missed samples
0
Samples dropped from the send buffer
0
Sequence gaps at the consumer
0
Sidecar processor load
15 to 16%

What this run shows. This has not been run against the physical sensor. The send buffer holds about 10 seconds. A broker outage longer than that loses the oldest samples.

Limits

How to read these results.

  • OpenSy polls. A change shorter than the gap between two reads is not seen. Latch or buffer a faster event in the PLC and read the latched value.
  • A direct read takes about 5 ms. A read routed through a chassis took about 10 ms in the welder run.
  • PLC-5 and SLC files, text tags, and Modbus registers are read on the machine scan. They do not use the fast channel.
  • A Kinetix attribute is read no faster than every 100 ms, because each request passes through the module that carries the drive’s motion traffic.
  • These are results from Miller Controls & Systems’ own testing. They are not third-party certifications.

Want a result for your controller?

Send the controller family and the network path. Engineering will say what has been run and what has not.