Fast signal from a ControlLogix on the same switch
The Windows Cincoze bench IPC and a ControlLogix on one switch. One signal read every 5 ms for 20 seconds. Five runs.
- Samples per second
- 198
- Sample spacing, median
- 5 ms
- Sample spacing, 99th percentile
- 6 ms
- PLC read to MQTT subscriber, median
- 2.8 ms
- Samples lost through the broker or into history
- None
- Worst gap across the five runs
- 7 to 14 ms
- Gaps longer than 10 ms
- About 1 in 4,000
What this run shows. The long gaps were single PLC reads that came back late. A routed controller or a slower network raises the read round trip and lowers the rate.